How Can I Enable and Configure Analog Inputs on CANopen OTB in SoMachine?

Published date: 05 September 2018

To  enable and Configure Analog Inputs on CANopen OTB in SoMachine please follow the steps below:

1. Double-click the node of your analog CANopen device in the Devices tree.
2. In the CANopen Remote Device tab of the editor, enable the option Enable Expert Settings.
Result: Additional tabs are displayed and the Service Data Object tab is populated with information.
3. Open the Service Data Object tab and click the New... button.
Result: The Select item from object directory dialog box is displayed.
4. From the list of objects, select object 6423, enter 1 as Value, and click OK.
Result: Analog input transmission on the CANopen bus is activated. You can now configure parameters of the analog values as described in the hardware manual of your device.