Browse FAQs

Why does the drive not stop when the run command is removed?

Published date: 20 February 2019

Issue:  
The drive does not stop, when the run command is removed.
 
Product Line:
Altivar 61, Altivar 71, Altivar 312, Altivar 212, Altivar12, Altivar 32
 
Environment:
All serial numbers
 
Cause:
The VFD is not responding to the stop command.
 
Resolution:
1).  Verify how the drive is receiving the stop command.
2).  Verify if the drive is programmed to get the stop command from that source. 
3).  Verify the drive is not in local control.
4).   Check if the run signal is jumpered/bypassed

Was this helpful?

What can we do to improve the information ?

Can't find what you are looking for?

Reach out to our customer care team to receive information on technical support, assistance for complaints and more.