Does the ATV61 have two different run inputs?

Published date: 09 May 2019

Issue:
Does the ATV61 have two different run inputs?

Product Line:
ATV61

Environment:
All models and serial numbers

Cause:
None

Resolution:
The ATV61 drive can only have a single run command at a time.  Logic input 1 (LI1) is the default run forward input when operating in 2-wire terminal control, and it cannot be changed.  When in 3-wire control, LI2 is the run forward input, and it cannot be changed. The run button on the keypad can also be used to run the motor when in HMI (keypad) control.