What does ramp increment mean for the Altivar 61/71?

Issue: 
What does ramp increment mean for the Altivar 61/71?
 
Product Line:
Altivar 61, Altivar 71
 
Environment:
All serial numbers
 
Cause:
N/A
 
Resolution:
Ramp increment is a parameter that will change the resolution of the listed parameters:  see below
Inr M [Ramp increment] 0.01 - 0.1 - 1 0.1
0.01   [0.01]: Ramp up to 99.99 seconds
0.1     [0.1]: Ramp up to 999.9 seconds
1        [1]: Ramp up to 9,000 seconds
This parameter is valid for [Acceleration] (ACC), [Deceleration] (dEC), [Acceleration 2] (AC2) and [Deceleration 2]
(dE2).             