What are the Publish and Receive Gooses Capacity for Sepam and CET 850 in IEC61850 Protocol?

Published date: 15 March 2019

Issue   
Customer would like to know the capacity for GOOSE messaging. 

Product Line    
IEC 61850
Sepam 80 Series

Environment    
communications

Resolution
For GOOSE publishing there isn't a maximum limit. Only the limit to 100% has to be respected.

For GOOSE receive messages there are a maximum of 40 GOOSE subscriptions for each IED/ ICD file.
For each Sepam there are 31 GOOSE receive messages when using the SFT 2841 to program.

 