Browse FAQs

How can I prevent Undervoltage faults on ATV61 drives?

Published date: 10 April 2019

Issue:
Needs to  prevent Undervoltage faults on ATV61 drives.

Product line:
ATV61, Altivar 61, ATV71, Altivar 71

Environment:
All

Cause:
Temporary voltage drops are causing UVR - Under voltage fault

Resolution:
Go to Drive Menu > 1.8 Fault Management > Undervoltage Mgt.  Change the Undervoltage timeout from 0.2s to somewhere between 5-10s. 

If the line voltage is less than 480VAC, we can also look at adjusting the Mains Voltage setting to 460V which lowers the trip level for the Undervoltage fault. 
 

Was this helpful?

What can we do to improve the information ?

Can't find what you are looking for?

Reach out to our customer care team to receive information on technical support, assistance for complaints and more.