How do you set up the analog output or AO1 on the ATV61 and ATV71 drives?

Published date: 26 April 2019

Issue:
How do you set up the analog output or AO1 on the ATV61 and ATV71 drives?

Product Line:
Altivar ATV61 and ATV71

Environment:
All

Cause:
Needs to set up the analog output for frequency with min 4mA and max 20mA.

Resolution:
Programming
Menu 1.5 I/O or inputs and outputs
AO1 assignment
Assign to motor frequency
Type: current
Min 4mA Max 20mA
 