How do you set up a run permissive on the S-Flex enclosed or ATV212 drives?
Issue:
How do you set up a run permissive on the S-Flex enclosed or ATV212 drives?
Product Line:
Altivar ATV212 and S-Flex enclosed
Environment:
All
Cause:
The ATV212 drive is not shutting down when they open the permissive input on R.
Resolution:
Check the programming
Find F------ codes enter
Find F100= this needs to be set to 0
Find F112= this if the R input assigned as the permissive. Set this to 1
Now when you open the R digital input the drive will shut down and display OFF.