Browse FAQs

How is the Otr (motor torque) parameter calculated on the ATV61 and ATV71 drives?

Published date: 08 May 2019

Issue:
How is the Otr motor torque parameter calculated on the ATV61 and ATV71 drives?

Product Line:
Altivar ATV61 and ATV71

Environment:
All

Cause:
Needs to know how the motor torque Otr parameter is calculated

Resolution
The torque of motor (OTR) is not measured by the drive. It is calculated from the measurement of motor current.
OTR = (Iq / Iqn) * (PhirdRef / Phirn) in %
With:     Iq : Current torque provide by the command to drive motor
             PhirdRef : Flux provide by the command to drive motor
             Iqn : Nominal Current torque compute with the motor name plate
             Phirn : Nominal flux of the motor
The maximum accuracy of motor torque is 5% (in closed loop). It can be up to 15% in open loop.
Concerning the range, OTR is expressed in % of nominal motor torque.
100% = Nominal motor torque.
OTR value is signed with minimum value -300% and maximum value 300%

Was this helpful?

What can we do to improve the information ?

Can't find what you are looking for?

Reach out to our customer care team to receive information on technical support, assistance for complaints and more.