How do you program an auto/manual or com via digital input on the ATV630 and ATV930 Process drives?

Published date: 09 July 2019

Issue:
Setup the Hand/Off/Auto on the ATV630/ATV930 Process drives.

Product Line:
Altivar ATV630 ATV930 Process drive

Environment:
All

Cause:
Wants to be able to wire in an HOC or HOA for switching between hand of auto or hand off communctions.

Resolution:
Example 1  hand off auto with terminal  start stop control in both modes. 
Main Menu enter
Complete Settings enter
Menu 5.4  command and references enter
Ref Freq 1 config = AI1 for hand control or Pot
Control mode= not seperate 
Freq switch assign= DI3   logic is DI3 = low = hand or  DI3= high= Auto 
Ref Freq 2 Config= AI3 for auto control 4-20mA 

Example 2 hand off com 

Main Menu enter
Complete Settings enter
Menu 5.4  command and references enter
Ref Freq 1 config = AI1 for hand control or Pot
Control mode= I/O Profile
CMD swtiching = DI3
CMD channel 1= terminal mode
CMD channel 2 = Ethernet 
Freq switch assign= DI3
Ref Freq 2 Config= Ethernet
Logic = DI3= low  Pot speed and terminal contorl or DI3= high Ethernet command and speed reference. 



 