Why does my numeric display show the wrong float value?

Published date: 28 October 2019

Issue:
Float value on the Magelis HMI is appearing incorrectly. 

Product Line:
Vijeo Designer Runtime (all versions)

Resolution
When using REAL data types on your PLC, ensure to use the Float numeric display. Otherwise, if you use an Integer numeric display with a REAL data type, the values will be off and look incorrect.