How can I ensure that my Magelis HMISCU starts in Run mode after a power cycle?

Published date: 29 May 2019

Issue
How can I ensure that my Magelis HMISCU starts in Run mode after a power cycle?

Product Line
EcoStruxure Machine Expert / SoMachine v3.1 and higher

Environment
SoMachine Logic Builder and Vijeo Designer configuration software in Windows

Resolution
To put the Magelis HMISCU controller RUN at startup:

1) Make sure the "Start All applications after a download or online changes" is selected



2) Create a Vijeo Designer action to write a non-zero value to @prop:0 on startup.

2.1) Create a new external variable INT in Vijeo Designer and address it as @prop:0.


2.2) Create an action to write a non-zero value to the variable on startup.


List of all driver properties for the HMISCU that can be used as an Integer variable in Vijeo Designer:

@prop:0
  • Read/Write access
  • Writing any non-zero value will put the controller application in RUN

@prop:1
  • Read/Write access
  • Writing any non-zero value will put the controller application in STOP

@prop:2
  • Read-Only access
  • This returns an integer that is associated with the state of the controller
    • 0 - N/A
    • 1 - Running
    • 2 - Stopped
    • 3 - Error
@prop:3
  • Read-Only access
  • This returns an integer that is associated with the Error state of the controller
    • 0 - No Errors
    • 1 - Error