How is the Start/Stop circuit wired for the ATS48 soft starter?

Published date: 06 August 2019

Issue:
Where do you wire the start run circuit for the ATS48 soft starter?

Product Line:
Altistart 48 ATS48

Environment:
All

Cause:
NA

Resolution:
For 2 wire control , jumper the RUN and STOP terminals and wire a run contact between the 24V and RUN terminals.

For 3 wire control, wire a N/C stop contact between 24V and STOP and wire a N/O start contact between 24V and RUN.