Is there an operation in Unity Pro that replaces the Concept M1HEALTH function block?

Published date: 21 May 2019

No.
The Concept M1Health function block was used to monitor local IO and distributed IO Bus slaves.
All of the same functionality can be reproduced in Unity Momentum with System Words.
Local IO Base can be monitored using %S119. 
IO Bus Health can be monitored using %S118. 
Slave Module Health can be monitored using %SW128, %SW129.