How to program an input on the ATV12 to freewheel stop?

Published date: 07 September 2018

Issue:
How to program an input on the ATV12 to freewheel stop?
 
Product Line:
Altivar 12
 
Environment:
All serial numbers
 
Cause:
N/A
 
Resolution:
To program an input to freewheel stop on the ATV12 use the following steps from RDY:
 
Press enter to rEf
Turn clockwise to ConF press enter.
Turn clockwise to Full press enter.
Turn clockwise to Fun press enter.
Turn clockwise to Stt- press enter.
Turn clockwise to nSt press enter.
Select the input  to use for nSt press enter.
Esc back to the beginning and cycle power.