Does the ATS22 Soft Starter use 24vdc control voltage?

Issue:
Does the ATS22 Soft Starter use 24vdc control voltage?

Product Line:
Altistart 22

Environment:
All products of ATS22

Cause:
N/A

Resolution:
The ATS22 Soft Starters do not use 24vdc control voltage externally. The ATS22...S6 series uses external 220Vac and the ATS22...S6U series uses 120Vac.
Both have internal 24vdc (used to activate the logic inputs) but you would have to bring the appropriate control voltage to use the internal voltage.
 