How can you program the ATV61 or ATV71 drive so that you can run the drive without the motor connected to it?

Published date: 13 September 2018

Issue:
How can you program the ATV61 or ATV71 drive so that you can run the drive without the motor connected to it?

Product Line:
Altivar ATV61 ATV71

Environment:
All

Cause:
Needs to test the drive to see if there is a problem with the drive by running the drive open circuit, without the motor connected to it.

Resolution:
Go to menu 1.8 Fault management
Find Output Phase Loss, and set to NO

Go to menu 1.4 Motor Control
Find Motor Control Type, and set to V/F 2pts

Note: Make sure to set Output Phase Loss back to yes after testing is done.   Wear necessary protective equipment while testing with OPL set to off, voltage and current will be available at the output terminals of drive
 