Can I connect to a SoMachine controller using the bluetooth adapter TCSWAAC13FB?

Published date: 04 September 2018


This is possible with SoMacihne V4.3.
 

Due to the fact that HMISCU COM (RJ45 connector) pin 7 does not provide power to the connected device it won’t work with the SCU. The other controllers provide 5V to this pin so that the adapter is powered.