Browse FAQs

Why can't I program the Pulse Width MOdulation Function Block in SoMachine Basic ver 1.3?

Published date: 30 November 2018

If the function block is bank when inserted into a rung, the Pulse Generators have not been setup in your Configuration. In the Configuration Tab under "My Controller" select "Pulse Generators" Select %PWM0 configuration and set the Time base and Preset for the pulse generator. Select apply and now you can use the function block in your logic.

Was this helpful?

What can we do to improve the information ?

Can't find what you are looking for?

Reach out to our customer care team to receive information on technical support, assistance for complaints and more.