Can the remote keypad of the S-Flex drive be removed without interrupting the drive operations?

Published date: 05 February 2019

Issue:
Removing the remote keypad with the drive running.

Product Line:
S-Flex ATV212

Environment:
All models

Cause:
None

Resolution:
Under typical Remote mode operation, removing the keypad while the VFD is running the motor will not interrupt the operation of the drive.

Two scenarios that will result in an Err9 fault when the keypad is removed are:
1) if running the VFD in Local mode
2) if the VFD is programmed for PID control and the setpoint source is FMOd=3