How can you program the ATV21 or ATV212 drive so that you can run the drive without the motor?

Issue:
How can you program the ATV21 or ATV212 drive so that you can run the drive without the motor?

Product Line:
Altivar ATV21 ATV212 S-Flex enclosed

Environment:
All

Cause:
Needs to test the drive to see if there is a problem with it, wants to run the drive open circuit without the motor connected to it.

Resolution:
Programming
Find F- - - Enter
Scroll to Output Phase Loss F605= 0 (Disable)
Set supply voltage correction F307 to 2 (supply voltage uncorrected).
Now you can disconnect your motor leads, and run the drive open circuit to test.
 