Shanghai Metro ensures reliable power for safe, stable and efficient rail operations with EcoStruxure.
Chart your energy career with our +200 free, vendor-neutral e-learning courses in more than 13 languages.
Access our mobile catalog, 24/7 support as well to expert help and tailored services on the go!
Globalization and digitization are shaping the future of energy and industries in the Age of 4th Industrial Revolution.
ENGLISH | FRENCH
You can choose another country to view available products or go to our Global website for company information.
Technical FAQs
Issue: What is the deceleration ramp time range for an ATS48 ?
Product Line: ATS48
Environment: All Cause: Maintenance
Resolution: ATS48 Deceleration ramp time ranges from 1 second to 60 seconds.