Will the ATS22 display light up with control voltage only?

Published date: 23 January 2019

Issue:
Will the ATS22 display light up with control voltage only?

Product Line:
ALTISTART 22

Environment:
All
 
Cause:
Troubleshooting

Resolution:
Yes, the display should light with control voltage applied.  

If the display does not light up:
Disconnect any remote HMI that you may have connected
Verify the correct control voltage is measured at the ATS22 terminals CL1 and CL2
    For models ATS22...S6 and ATS22...Q the control voltage should measure ~230vac
    For models ATS22...S6U the control voltage should measure ~110vac