Do the ATV61 and ATV71 drives have a built in ON delay timer for the logic inputs?

Published date: 22 February 2019

Issue:
Needs a built in ON delay timer for the logic inputs on the ATV61 and ATV71 drives.

Product line:
Altivar 61 & 71

Environment:
All models, all serial numbers.

Cause:
Customer needs to delay the run command after LI1 closes. 

Resolution:
Using the HMI or keypad, under Menu 1.5 Inputs/Outputs CFG, go to LI1 Configuration and select LI1 On Delay. 
The default setting for this parameter is 0 ms, but can be set to 0 to 200ms. 
The time delay function is available on all the logic inputs.