Can you read the parameters on the ATV212 drive via Lonworks that do not have a SNVT assigned?

Published date: 29 July 2019

Issue:
Can you read the parameters on the ATV212 drive via Lonworks that do not have a SNVT assigned?

Product Line:
ATV212, ATV61, ATV71

Environment: 
All VFD with LonWork communication

Cause
Communication

Resolution:
To access parameters on the VFD via lonworks that is not available by SNVTs, use the nvIParamCmd  and the nvoParamResp

For more details, please see: ATV212_LonWorks_manual_EN_S1A53848_01.pdf