Browse FAQs

On the ATV312, what is parameter CL1?

Published date: 13 August 2019

Issue:
 ATV312, wondering what is parameter CL1?

Product Line:
ATV312

Environment:
All

Cause:
None

Resolution:
CL1 sets a threshold to limit the current output to the motor.  It is used to limit stress on the motor and load when conditions are abnormal.
Typically this value is set at 1.2 X motor FLA for variable torque loads and at 1.5 X FLA for constant torque loads.

Was this helpful?

What can we do to improve the information ?

Can't find what you are looking for?

Reach out to our customer care team to receive information on technical support, assistance for complaints and more.