How do you set up the ATV61 drive to be used with the VW3A3314 Apogee P1 option card?

Published date: 11 October 2018

Issue:
How do you set up the ATV61 drive to be used with the VW3A3314 Apogee P1 option card?

Product Line:
Altivar ATV61 with VW3A3314 option card.

Environment:
All

Cause:
Needs setup assistance with the ATV61 and Apogee P1 card.

Resolution:
Card connector Pin outs

Contact B= (+) signal
Contact A= (-) signal
Contact GND= (GND)
Contact SCR= (Shield)

Programming Drive  ( You must Power cycle after changing any of the Menu 1.9 coms parameter settings)
Menu 1.9- Communications (CON)
Address range is 0-99  (Choose your address)
Baud rate: Choose between 4800 to 76800
Network time out = range is 2 to 60 seconds (Choose your network time out)

Menu 1.6 Command menu
Controlling the drive over the network
Ref 1 = Com card
Profile is Not separate
Point # 24 (LDO  table) is your start command for CMD  (writing a 1 will start 0 will stop)
Point # 60 (LAO table) is your input speed reference 1 in %
Note: If the drive will not start with writing a 1 to Point #24 try writing a 0 to #24 1st then writing a 1.

Reading data only from the drive.
Ref 1 AI1
Profile not separate
Point #03= freq output in hz
Point #05= speed output in rpms
Point # 06= Motor current
Point # 07= Motor Torque
Point # 08= Motor Power
Point # 09 = Drive Temp
There are other values that you can read in the LAI table see the attached document for information.