Why would you be unable to assign reference 2 channel to LI3 via SoMove light?
Issue:
Unable to assign reference 2 Switching to LI3 via SoMove light.
Product Line:
Altivar 61, Altivar 71
Environment:
Firmware revision 5.8 and later, Somove version 1.9.4.0 and later
Cause:
SoMove will not allow the customer to change Reference 2 switching to LI3.
Resolution:
Ensure that the parameter profile is not set to Not Sepr (Not Separate). After setting profile to Separate, the customer was able to make the needed change.