Does Schneider Electric offer a drive for 480 vac three phase motor with a 480 vac single phase input voltage?

Published date: 20 April 2019


Issue:
Customer needs a drive for a 460 VAC 50 HP motor, 460 V with single phase power. 

Product Line:
Altivar drives

Environment:
All

Cause:
Customer's site only has 480 V single phase line voltage available.

Resolution:
The ATV320 and ATV630 product lines have models that are rated for 480V single phase supply.
See the attached Annex files for details.

Contact the local Drives Product Application Engineer (PAE) or Sales office for approvals of other VFDs for use with 480V single phase supply.

The Annex is the only approved document, so all previous documentation including Pricing Guides, Errata sheets and the letters from Product Management are superseded by these documents and all inquiries regarding this type of application need to be referred to the appropriate published document.

For any 480 V single phase applications outside of the approved ATV320 models, consider contacting Bonitron (http://www.bonitron.com/drive-schneider.html) for possible solutions such as supplying DC voltage direct to the VFD DC bus.  The ATV630 does not have terminal access to the DC bus.