What causes Unity error "Due to alignment constraint, you have to decrease or increase topological address index of 1"?

In Unity Pro, 32 bit datatypes must be mapped to an even address boundary when using the M340 PLC.
For example,   variables  of REAL or DINT datatypes must be mapped to %MW2, not %MW1.