Repetitive "Invalid Device Security" Errors Seen in the System Log

Published date: 15 March 2019

Issue
The Log Inserter is unable to upload any data, and when the System Log is scanned, a continuous stream of errors, reported by Treemon, are seen. The error description is similar to:

"Description Invalid device security settings for office.the8650"

Product Line
ION Enterprise
Struxureware Power Monitoring
Power Monitoring Expert
ION Devices

Environment
Advanced Security

Cause
A device that supports Advanced Security has security enabled, but has not been configured for security within the Management Console.
 

Resolution
Using the Management Console, select the device referenced in the event, right-click and choose Security from the pop-up menu. Select the Advanced Security module that is to be used:

Click on "Change Password" to enter the password for this security module, click OK:

 