What modbus address or word shows you motor speed in rpm's on the ATV61 and ATV71 drives?
Issue:
What modbus address or word shows you motor speed in rpm's on the ATV61 and ATV71 drives?
Product Line:
Altivar ATV61 and ATV71
Environment:
All
Cause:
4X modbus address word showing rpm's motor speed.
Resolution:
rFrd= Output speed in rpm's modbus address 8604
rFr= Output frequency in hz modbus address 3202
Please note you might have an offset when reading the modbus addresses.