Which measurements are used by the Energy Cost and Load Profile reports?

Published date: 22 March 2019

Issue
The Energy Cost and Load Profile reports require that data is logged to specific measurements in order to run. 

Product Line 
ION Enterprise 6.0 SP1
Struxureware Power Monitoring 7.0.x
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.x
Power Monitoring Expert 9.0

Environment
Web Applications Reports

Cause
The Energy Cost, and Load Profile reports have a list of possible measurements that it looks for in a specific order. The default order is indicated below, but note that the order can be configured or additional measurements can be added via a SQL query or by editing the view directly in Management Studio. This list of measurements is read from the database its an entry in vCFG_ConfigItems (a view in ION_Network)

Resolution
Energy Cost Report:

kWh:
Active Energy Delivered-Received - ID135
Active Energy Delivered+Received - ID198
Active Energy Delivered ID129
Active Energy Received Rate A ID130
Active Energy Delivered Interval ID134
Active Energy Received Interval ID144

MeasurementID Labels Mapped To This Measurement
135 kWh del-rec
kWh net
Real Energy Signed
Real Energy
198 kWh del+rec
kWh tot
Real Energy Absolute
129 kWh del,
kWh imp, kWh
kWh tot del
Real Energy into the Load
130 kWh del A
kWh del tariff 1
134 kWh del int
kWh imp int
Real Energy Delivered Interval
144 kWh rec int
kWh exp int
Real Energy Received Interval


kVARh:
Reactive Energy Delivered-Received ID97
Reactive Energy Delivered + Received ID191
Reactive Energy Delievered ID91
Reactive Energy Received Rate A ID92
Reactive Energy Delivered Interval ID96
Reactive Energy Received Interval ID106
 
Measurement ID Labels Mapped To This Measurement
97 kVARh del-rec
kVARh net
Reactive Energy Signed
Reactive Energy
191 kVARh del+rec
kVARh tot
Reactive Energy Absolute
91 kVARh del
kVARh imp
kVARh
Reactive Energy Into the Load
92 kVARh del A
kVARh del tariff 1
96 kVARh del int
kVARh imp int
106 kVARh rec int
kVARh exp int

kVAh:
Apparent Energy Delivered + Received ID63
Apparent Energy Delivered-Received ID740
Apparent Energy Delivered ID489
Apparent Energy Delivered + Received Rate A ID2659
 
MeasurementID Labels Mapped To This Measurement
63 kVAh
kVAh del+rec
kVAh tot
Apparent Energy
740 kVAh net
kVAh del-rec
489 kVAh del
kVAh imp
2659 kVAh tariff 1


kW:
Active Power Sliding Window Demand Delivered-Received ID107
Active Power Sliding Window Demand Delivered+Received ID738
Active Power Sliding Window Demand Delivered ID116
Active Power Thermal Demand Delivered-Received ID117
Active Power Sliding Window Demand Received ID739
 
MeasurementID Labels Mapped To This Measurement
107 kW sd del-rec
kW swd
kW tot swd
kW Dmd del-rec
Demand Real Power Sliding
Demand Real Power
738 kW sd del+rec
116 kW demand
kW sd del
kW tot SD
117 kW td del-rec
Demand Real Power - Thermal
739 kW sd rec

kVAR:
Reactive Power Sliding Window Demand Delivered Received ID69
Reactive Power Sliding Window Demand Delivered+Received ID735
Reactive Power Sliding Window Demand Delivered ID78
Reactive Power Thermal Demand Delivered-Received ID79
Reactive Power Sliding Window Demand Received ID737
 
MeasurementID Labels Mapped To This Measurement
69 kVAR sd del-rec
kVAR swd
kVAR Dmd del-rec
Demand Reactive Power Sliding
Demand Reactive Power
735 kVAR sd del+rec
78 kVAR demand
kVAR sd del
kVAR tot SD
79 kVAR td
kVAR td del-rec
Demand Reactive Power - Thermal
737 kVAR sd rec

kVA:
Apparent Power Sliding Window Demand Delivered+Received ID37
Apparent Power Sliding Window Demand Delivered-Received ID736
Apparent Power Sliding Window Demand Delivered ID573
Apparent Power Thermal Demand Delivered+Received ID47
 
MeasurementID Labels Mapped To This Measurement
37 kVA sd del+rec
kVA swd
kVA Dmd
Demand Apparent Power - Sliding
736 kVA sd del-rec
573 kVA demand
kVA sd del
kVA tot SD
Demand Apparent Power
47 kVA td

Load Profile Report:

Active Demand:
Active Power Sliding Window Demand Delivered-Received ID 107
Active Power Sliding Window Demand Delivered+Received ID 738
Active Power Sliding Window Demand Delivered ID 116
Active Power Thermal Demand Delivered-Received ID 117
Active Power Sliding Window Demand Received ID 739
 
MeasurementID Labels Mapped To This Measurement
107 kW sd del-rec
kW swd
kW tot swd
kW Dmd del-rec
Demand Real Power Sliding
Demand Real Power
Panel-Main Demand Real Power
738 kW sd del+rec
116 kW demand
kW sd del
kW tot SD
117 kW td del-rec
Demand Real Power - Thermal
739 kW sd rec

Reactive Demand:
Reactive Power Sliding Window Demand Delivered Received ID 69
Reactive Power Sliding Window Demand Delivered+Received ID 735
Reactive Power Sliding Window Demand Delivered ID 78
Reactive Power Thermal Demand Delivered-Received ID 79
Reactive Power Sliding Window Demand Received ID 737
 
MeasurementID Labels Mapped To This Measurement
69 kVAR sd del-rec
kVAR swd
kVAR Dmd del-rec
Demand Reactive Power Sliding
Demand Reactive Power
735 kVAR sd del+rec
78 kVAR demand
kVAR sd del
kVAR tot SD
79 kVAR td
kVAR td del-rec
Demand Reactive Power - Thermal
737 kVAR sd rec

Apparent Demand:
Apparent Power Sliding Window Demand Delivered+Received ID 37
Apparent Power Sliding Window Demand Delivered-Received ID 736
Apparent Power Sliding Window Demand Delivered ID 573
Apparent Power Thermal Demand Delivered+Received ID 47
 
MeasurementID Labels Mapped To This Measurement
37 kVA sd del+rec
kVA swd
kVA Dmd
Demand Apparent Power - Sliding
KVA SD
736 kVA sd del-rec
573 kVA demand
kVA sd del
kVA tot SD
Demand Apparent Power
47 kVA td
kVA td del+rec
Demand Apparent Power - Thermal


Power: for devices that dont do SWD
Active Power ID193
Reactive Power ID187
Apparent Power ID544
 
MeasurementID Labels Mapped To This Measurement
193 kW tot
kW total
Real Power Total
187 kVAR tot
kVAR total
Reactive Power Total
544 kVA tot
kVA total
Apparent Power Total