Is there an example on how to program a "Flasher Circuit" using 984 Ladder Logic that can be used as an annunciator?

Below is a 984 Ladder Logic example of a "Flasher Circuit". The first Timer is the "Off" time and the second Timer is the "On" time. The example is a 1 second "Off" and 1 second "On" for output 00001..