Implementing CIP Explicite messaging to Modbus object between a 140NOC78000 (client) and a 140NOC78000 (server)

Goals and Symptoms

When using the 140NOC78000 as a server, to get process data through the Modbus object, only Unconnected_ Send messaging will work. The attachment is an example on how to perform an Explicit messaging using the MBP_MSTR block from a 140NOC78000 client.

Causes and Fixes

Using UCMM and connected messaging will only return diagnostic data when communicating to a 140NOC78000


(Removed File URL: 210063_3A36/140NOC78000_CIP_Modbus_Object_Read.ppt)(Removed Image URL: /PubResEXPORT.nsf/2b87ee90be777fc085257c28006ee4ef/66b765187fc1a580c1257ad800161c56/fl_block_5/0.114?OpenElement&FieldElemFormat=gif)

Legacy KB System (APS) Data: RESL210063 V1.0, Originally authored by DaDz on 12/18/2012, Last Edited by DaDz on 12/18/2012
Related ranges: Modicon Quantum