What impact does setting %MWi Reset on Cold Start have after a download of my application to the Quantum CPU?

If the %MWi Reset option is selected any %MW reference in the Data Editor which has an assigned value can expect that value to be transferred to the CPU on a Cold Start.
If the %MWi Reset option is de-selected all %MW values in the PLC will be initialized to zero, regardless of whether there are values in the Data Editor for the %MW references.. 


 