What does "BUSY" mean when I do a "Netscan" with ProWORX NxT?

Title
What does "BUSY" mean when I do a "Netscan" with ProWORX NxT?

Issue
"BUSY" meaning when I do a "Netscan" with ProWORX NxT

Product Line
ProWORX NXT

Environment
ProWORX NXT

Cause
When doing a "Netscan" with ProWOX NxT, "BUSY" means that the Modicon PLC is already "Logged On" for Programming privilege by another computer. Only 1 Programming Device can be "Logged On" at any one time.

Resolution
 To correct the problem, you must find out which computer is "Logged On" and "Log Off".