Are services such as Ethernet IO Scanner or Global data active in a Standby unit within a Hot Standby System?

Published date: 15 March 2019

Not completely. IO Scanner is halted in the Standby unit but Global Data may send out GMRP and IGMP 'Join' messages to inform Ethernet switches supporting GMRP/IGMP for switch multicast table management. Global Data does not actively publish, nor subscribe in Standby mode.


Legacy KB System (APS) Data: RESL173819 V1.0, Originally authored by on , Last Edited by on
Related ranges: Modicon Quantum