Browse FAQs

Why does my Altivar drive have no display?

Published date: 28 January 2019

Issue:
MyAltivar drive does not have a display?

Product Line:
All Altivar drives
 
Environment:
Display doesn't light up
 
Cause:
n/a
 
Resolution:
Measure the input voltages (phase to phase) at L1, L2 and L3
Measure the DC bus at PA+ and PC-
Measure the +24v and +10v supplies. Measure to COM, not ground.
If the DC bus is ok, then could be a problem with the Main Control board and/or the Power Board, of the drive.
 
 
 


Was this helpful?

What can we do to improve the information ?

Can't find what you are looking for?

Reach out to our customer care team to receive information on technical support, assistance for complaints and more.