What is the minimum cancelling time of the power supply voltage for the Sepam 1000+ without its reinit (restart)?

Effects of interruptions of the DC power supply. (CEI60255-11)
The effects are determined for an interruption with a duration chosen in the following list and declared by the manufacturer : 2 _ 5 _10 _ 20 _ 50 _ 100 _ 200 ms

The interruption must be sudden, i.e.the auxiliary power supply must vary from 0 to the rated value and the opposite .

The relay must not change erroneously its output status when the power supply value is applied or cancelled.

Fugitive cancellings Sepam 1000+ S20: 10ms.
Fugitive cancellings Sepam 1000+ S40: 20ms.
Fugitive cancellings Sepam Series 80: 100ms

Re-published to revised security level: 17 June 2008 by DRM

Applies To: Sepam 20, 40, and 80