What are possible causes of SCF1 motor short circuit faults on the ATV61 and ATV71?

Issue:
What are possible causes of SCF1 motor short circuit faults on the ATV61 and ATV71?

Product Line:
ATV71 Altivar 71

Environment:
All

Cause:
SCF1 [Motor short circuit]     Short-circuit or grounding at drive output

Resolution:
  • Check the cables connecting the drive to the motor, and the motor’s insulation
  • Perform tests via the [1.10 DIAGNOSTICS] menu.​
  • Run the drive open circuit (with the motor disconnected and OPL turned off) and check the drive's output terminals for balanced voltages phase to phase
  • Perform a diode check between U,W,V and PA+ PC-. Then measure between L1, L2, L3 and PA+ and PC-: 
NOTE: This step should be performed when no line voltage is present on the drive. Power down the drive before performing this step. 
-Measure (using your meter's diode  scale) in one direction, then swap your leads and measure again
-You should see 'OL' in one direction and a small voltage reading (approximately 0.3-.0.5V) in the other direction
    