Is there a PID loop feature on ATV12 drives?

Published date: 15 July 2019

Issue:
Is there a PID loop on ATV12 drives?

Product Line:
Altivar ATV12

Environment:
All

Cause:
PID loop set up

Resolution:
Yes, PID regulator settings can be found under the FuN menu.
[Conf] -> [Full] -> [Fun]
At 'PId' press Enter
PIF= PID feedback assignment Set to AI1 (Choice not possible if Fr1 is set to AI1)
PII= Activation of internal PID reference (Yes or No)
rP1= internal PID reference  (0 to 100%)
rPL= PID min value reference (0 to 100%)
rPH= PID max value reference (0 to 100%)

For further details, please see the ATV12 User Manual starting on page 72.