What is an INF7 fault on the ATV61 and ATV71 drives?

Published date: 15 October 2019

Issue:
What is an INF7 fault on the ATV61 and ATV71 drives?

Product Line:
Alitvar ATV61 and ATV71

Environment:
All

Cause:
Internal hard initialize fault

Resolution:
INF7 is a EEPROM initialization fault on the main control board.  Try power cycling to clear if it will not clear you may have to replace the main control board or replace the drive.