Technical FAQs
Issue: bPF fault on the ATS22 soft starter
Product Line: Altistart ATS22
Environment: All
Cause: Bypass contactor detected fault
Resolution: Check for a welded bypass contactor or shorted SCR If you find a shorted SCR or bypass contactor you will need to replace the soft starter. Reference manual BBV51330 ATS22 installation guide.