Browse FAQs

Where can I find basic programming information for ATV32?

Published date: 01 February 2019

Issue:
Looking for basic programming information for ATV32?

Product Line:
Altivar ATV32

Environment:
All

Cause:
Programming configuration set up

Resolution:

CONF>FULL>SIM  

bFr= Base motor frequency 60hz
nPr= HP of he motor 
UnS= Rated motor voltage 
nCr= Rated motor current (motor FLA)
FrS= Rated motor frequency 
nSP= Ratd motor speed (rpm's on motor nameplate)
tFr= Max frequency
ItH= Motor thermal current (match motor FLA)
ACC= Acceleration (ramp up) time
dEC= Deceleration (ramp down) time
LSP= Low speed
HSP= High speed


Was this helpful?