How can you reset the Altistart ATS22 soft starter back to factory default?

Issue:
How is the ATS22 reset back to factory default?

Product Line:
Altistart 22, ATS22

Environment:
All

Cause:
Resetting current settings back to the original factory settings.

Resolution:
Hold the ESC and UP arrows at the same time for 5 seconds, then the display will show the Utility menu - UtIL.
Push the enter button. 
Use the arrow keys to scroll to parameter FCS, (Back to factory settings)
Push the Enter button. 
Push Enter once and you will get a prompt for "sure".  Push the Enter button again will reset the soft starter back to factory defaults. 