Technical FAQs

Ask a Question

How can you wire in a 0-10vdc speed reference on the ATV312 drive?

Issue:
Wiring and programming

Product Line:
All

Cause: 
Programming AI1 for an 0-10vdc speed reference.

Resolution :
Wiring external 2 wire 0-10vdc signal from a SCADA or building automation system.
Connect +10vdc to AI1 and 0V to com on the drive.

Wiring a external POT to control speed via AI1.
Connect the center wiper of the POT to AI1 and the other two legs will go to +10vdc and com.

Programming so that AI1 is the speed reference.
CtL menu set Fr1 to AI1 (factory default setting)
Was this helpful?
What can we do to improve the information ?