How do you wire a remote potentiometer to an ATV12 drive?

Published date: 12 October 2018

Issue: 
How do you wire a remote potentiometer to an ATV12 drive?

Product line:  
Altivar ATV12 
 
Environment: 
All models, all serial numbers 
 
Cause:  
Field wiring a remote pot into the ATV12 drive.     
 
Resolution:
Wiring as follows:  The potentiometer's wiper is connected to AI1, high side of the pot wires to +5 V and low side of pot wires to COM.
You have the option of using your own +10VDC source if +5VDC off the drive is not wanted.