Browse FAQs

E-Flex Altivar 61 How can I invert the mA analog input signal?

Published date: 01 November 2018

Issue:  
How can you invert the mA signal so the drive runs at low speed at 20mA and high speed at 4mA?

Product line:
Altivar ATV61, ATV71
 
Environment:
All models, all serial numbers

Cause:
 Inverting the mA analog input signal

Resolution:
Menu 1.5 AI2 configuration AI2 min set to 20mA and  AI2 max set to 4mA
ATV71_programming_manual ref  

Was this helpful?

What can we do to improve the information ?

Can't find what you are looking for?

Reach out to our customer care team to receive information on technical support, assistance for complaints and more.