Published date: 01 August 2019

Issue:
Programming RY Relay for Run Status on ATV212 Drives.

Product line:
Altivar 212  

Environment:
All models, all serial numbers   

Cause:
Need for a signal from the drive indicating that the motor is running.

Resolution:
Wire to RYA and RYC relay and program F130 to 14 (drive running).  The relay will close if a run command is issued and there are no faults.

 